SMA Cluster Controller

Be the first to review this product

Availability: In stock

$1,539.99
OR

Quick Overview

  • Allows you to monitor up to 75 string inverters.
  • Robust enclosure for industrial settings
  • Professional monitoring and controlling for large decentralized PV plants
  • SMA Cluster Controller

    More Views

    Details

    CLON-10 SMA Cluster Controller

    The SMA Cluster Controllers allows you to monitor up to 75 string inverters with email notification of inverter failure.
    Remote monitoring and maintenance over Sunny Portal.
    Robust enclosure for industrial settings
    Professional monitoring and controlling for large decentralized PV plants

    Features:

  • Monitors and controls up to 75 string inverters
  • Exchanges real-time data with other devices and systems using the standard Modbus® communications protocol
  • Complies with national and international requirements for grid integration
  • Integrated analog and digital interfaces for sensors and active/ reactive power setpoints
  • Easy installation due to top-hat rail mounting and connectors
  • Optimized for industrial use, thanks to a robust enclosure and high-quality components
  • Easy installation due to top-hat rail mounting and connectors
  • Optimized for industrial use, thanks to a robust enclosure and high-quality components

    Specification

    Technical data

    Communication
    Brand Sm
    Manufacturer Part Number CLCON-10
    Inverters Speedwire, 10 / 100 Mbit/s
    Data network (LAN) Fast Ethernet, 10 / 100 Mbit/s
    Data interfaces HTTP, FTP, Modbus TCP/UDP, SMTP, Sunny Portal

    Connections

    Inverters / data network (LAN) 2 Ports, 10BASE-T or 100BASE-TX, RJ45, switched
    Data storage 2 USB 2.0 High-Speed sockets, Type A
    Voltage supply / analog/digital signals Connector, push-in cage clamp terminal
    Max. number of SMA devices (Speedwire) 75
    Max. communication range (Speedwire / LAN) 100 m (between two devices)


    Voltage supply

    Voltage supply External power supply unit (available as an accessory)
    Input voltage 18 V DC … 30 V DC
    Power consumption Typical 12 W / max. 30 W


    Ambient conditions in operation

    Ambient temperature −25°C … +60°C (−13°F … +140°F)
    Relative air humidity 4 % … 95 %, not condensing
    Altitude above sea level 0 m … 3000 m


    Display

    Type LC display, monochromatic, back-lit
    Display languages English, German


    Memory

    Interna 1.7 GB as ring buffer
    External USB mass storage (optional, available as an accessory


    Digital input

    Quantity 8
    Usage Specification for active and reactive power


    Analog inputs

    Quantity 3 x current signal, 1 x voltage signal
    Measuring range 0 mA … 20 mA or 0 V … +10 V
    Usage Irradiation measurement, specification for active and reactive power or current/voltage measurement


    Digital output

    Quantity / design 3 / potential-free relay contacts
    Max. load tolerance 48 V DC / 30 W
    Usage Error message, warning and active power limitation


    Analog output

    Number / signal current 2 / 4 mA ... 20 mA
    Usage Feedback of the active and reactive power setpoints


    General data

    Dimensions (W / H / D) 275 / 133 / 71 mm (10.8 / 5.2 / 2.8 inches)
    Weight 0.9 kg (2.0 lb)
    Mounting type Top-hat rail mounting
    Status display LC-Display, LEDs
    Software languages, languages of the manual German, English, Italian, Spanish, French, Dutch, Portuguese, Greek, Czech
  • Product Tags